Data centre noise control in Thailand

Noise control for standby generators, chillers, dry coolers and plant rooms, so a data centre in Thailand stays inside its boundary noise limits at night, when the margin is smallest, without giving up the airflow its cooling depends on.

Where the noise comes from

Data centre noise comes from five places: standby generator plant rooms, rooftop and external cooling plant, external plant compounds, the site perimeter, and the data halls themselves. Each one is solved differently.

Standby generators are the loudest items on site when they run. They run for testing and during outages. Chillers, dry coolers and air handling fans run continuously, including at night, so in most projects it is the cooling plant that sets the design rather than the generators.

The design case is the quietest period at the nearest sensitive receptor, which is normally night, not a daily average. Placing external compounds as far from those receptors as the site plan allows is cheaper than any attenuation.

The limits a Thai site is assessed against

LimitValueApplies toSource
Ambient noise, 24-hour averageLeq 24h not above 70 dBAGeneral environmentNational Environment Board Notification No. 15 (B.E. 2540 / 1997)
Maximum noise levelLmax not above 115 dBAGeneral environmentNational Environment Board Notification No. 15 (B.E. 2540 / 1997)
Annoyance noiseNot more than 10 dBA above the background (L90)Where people are affectedNational Environment Board Notification No. 29 (B.E. 2550 / 2007), method by the Pollution Control Department
Factory boundaryThe same three valuesPremises regulated as factoriesMinistry of Industry notification on factory noise (B.E. 2548 / 2005)
Occupational exposure85 dBA over 8 hoursStaff working inside plant roomsMinisterial Regulation on heat, light and noise B.E. 2559 (2016) and the Department of Labour Protection and Welfare notification B.E. 2561 (2018)

The annoyance test is the one that usually decides a data centre. It compares the level with the plant running, corrected upward where the sound is tonal or impulsive, with the background L90 measured without it. A difference of more than 10 dBA counts as annoyance. Because it is relative to the existing background, a site next to a quiet village at night has far less room than the 70 dBA headline suggests.

Data centres are currently permitted as buildings rather than as factories, and they do not appear on the project list that triggers an environmental impact assessment.

The draft data centre bill (2026)

A draft data centre bill was open for public comment from 3 September to 15 October 2026. As drafted, it would require a licence from the Ministry of Digital Economy and Society, siting in areas zoned for industry, an environmental and health impact assessment for every project, and noise and heat kept within limits set by the minister. It is a draft and may change. Projects being designed now in Chonburi, Rayong or Samut Prakan may want to allow for that assessment.

Status checked 27 October 2026.

Standby generator rooms

A generator plant room has to balance airflow against attenuation. Space for the intake and discharge attenuators has to be found before the structure goes up. Found afterwards, it becomes larger openings or bolt-on external silencers.

The engine exhaust is a separate path and takes its own silencer. Where emissions have to be reduced as well as noise, selective catalytic reduction can be integrated into the same exhaust assembly.

Containerised and skid-mounted sets are usually enclosed. The manufacturer states an enclosure range of roughly 15 dB(A) to more than 50 dB(A), depending on the design and how completely the source is enclosed. The cooling path, the discharge and the exhaust route have to be settled at the same time as the acoustic rating: an enclosure sealed tightly enough to reach a high figure will overheat the machine inside it.

Chillers, dry coolers and rooftop plant

Because this plant runs all night, it is usually the design case. Fan noise is often tonal, and tonal sound attracts a correction in the annoyance test, so tones are worth treating specifically rather than lowering the overall level alone.

Where air has to pass through the screen, louvred acoustic screens are used. Where it does not, absorptive barriers do more for the money. A barrier only works if it breaks the line of sight between source and receptor; height and position matter more than the mass of the panel. For absorptive free-standing barriers the manufacturer quotes transmission loss up to around 14 dB at 125 Hz.

Axial fan discharges can be treated with D-Duct diffuser attenuators directly at the fan.

Acoustic louvres: airflow against attenuation

Acoustic louvres are for openings where airflow has to be preserved, not where maximum attenuation is wanted. Those two things trade against each other every time, so a louvre is selected on free area and pressure drop alongside its attenuation. IAC supplies two ranges: Noishield, with curved blades, and Slimshield, with linear blades. Acoustic louvre doors for plant room walls are also available.

The values below are laboratory figures from IAC Acoustics' published datasheets.

ModelFree areaRw (dB)Dn,e,w (dB)Cd63 Hz125 Hz250 Hz500 Hz1 kHz2 kHz4 kHz8 kHz
Noishield LP52%11180.30458912976
Noishield 2LP52%19250.24258121622181514
Noishield R43%14210.2395711121314129
Noishield 2R43%24310.17612152124272520
Slimshield SL 10042%10160.22554569131413
Slimshield SL 15032%15210.1276681014181615
Slimshield SL 30045%17230.23367101218181413
Slimshield SL 60045%26310.16179122431332930
Octave-band columns are transmission loss in dB. Free area is the nominal value averaged over the louvre depth. Cd is the discharge coefficient: the higher it is, the less pressure the louvre takes from the airflow.

Two things follow from the published figures:

  • Low frequencies are a louvre's weak point. At 125 Hz the published transmission loss ranges from 4 dB (SL 100) to 12 dB (Noishield 2R). Generator and chiller noise is strong in exactly that band, which is why a generator room usually pairs its louvres with intake and discharge attenuators rather than relying on louvres alone.
  • More attenuation costs airflow. Noishield R and 2R have the same nominal free area, but 2R gains 10 dB of Rw at a discharge coefficient of 0.17 against 0.239. The opening has to be sized for the louvre that meets the target, not the other way round.

The installed result depends on the size of the opening, the airflow through it and any flanking paths, so the selection is confirmed for each project.

Inside the building: plant rooms, doors and data halls

Doors are the weak point of any plant room, so the rating of the openings has to be designed alongside the wall, not after it. Noise-Lock steel acoustic doors are made to the opening size and the rating the project specifies.

Absorptive wall and ceiling panels reduce the reverberant build-up inside a plant room, which helps at the boundary and for the staff inside, where the 85 dBA occupational limit applies.

Air handling for the data halls is treated in the duct. Silencers are selected on Dynamic Insertion Loss measured with air flowing, together with the self-noise the silencer generates, not on a no-flow figure.

What we need to quote

  • A site plan showing the boundary and the nearest sensitive receptors
  • The equipment schedule, with sound power or measured levels for each unit
  • Airflow, available pressure drop and the openings for each plant room
  • The target limit and where it comes from, normally an acoustic consultant's assessment based on a background measurement taken at night
  • The programme

Everything in this family is made to the project specification. We supply to the project; your contractor installs.

Where this is specified

  • Hyperscale and colocation data centres
  • Standby generator plant rooms and fuel compounds
  • Chiller yards and cooling tower compounds
  • Rooftop mechanical plant on offices and high-rise buildings
  • Site perimeters adjoining residential areas

Product lines in this family

  • Silencers for cooling plant and air intakes
  • Intake and discharge attenuators for generator plant rooms
  • Exhaust silencers for standby diesel engines
  • Acoustic enclosures for standby generators and chillers
  • Noishield acoustic louvres, curved blade
  • Slimshield acoustic louvres, linear blade
  • Louvred acoustic screens for chiller and dry cooler compounds
  • Absorptive barriers around plant compounds and site boundaries
  • D-Duct diffuser attenuators for axial fan discharges
  • Absorptive wall and ceiling panels for plant rooms
  • Noise-Lock steel acoustic doors for plant rooms and data halls

Frequently asked questions

What noise limits apply to a data centre in Thailand?
There is no limit written specifically for data centres yet. The general ambient limits are 70 dBA as a 24-hour Leq and 115 dBA maximum (NEB Notification No. 15, 1997). The annoyance limit is 10 dBA above the existing background (NEB Notification No. 29, 2007), and staff inside plant rooms fall under the 85 dBA occupational limit.
Which limit is usually the hardest to meet?
The annoyance limit, because it is measured against the existing background noise, and the background is lowest at night. A quiet rural or suburban site can leave a small margin.
Does a data centre need an EIA in Thailand?
Not at present. Data centres are permitted as buildings and are not on the EIA project list. A draft data centre bill put to public comment in September and October 2026 would require an environmental and health impact assessment for every project. Status checked 27 October 2026.
What is the noisiest equipment on a data centre site?
Standby generators, when they run. They run for testing and outages, while chillers, dry coolers and fans run continuously, so the cooling plant usually sets the night-time design.
When should generator room silencers be designed?
Before the structure is designed. Intake and discharge attenuators need wall space and plant room depth. Found later, they become larger openings or external silencers.
Acoustic louvre or acoustic barrier?
A louvre where air has to pass through the opening; a barrier where it does not. A louvre trades attenuation against free area and pressure drop. A barrier only works if it breaks the line of sight to the receptor.
Do you install?
No. IAC Acoustics (Thailand) supplies to the project, and the project's contractor installs with our fitting instructions.
Who measures the existing background noise?
An independent acoustic consultant, normally at night at the nearest sensitive receptors. We select equipment against the target that assessment sets. If you do not have a consultant yet, Geonoise carries out boundary measurements, noise predictions and commissioning measurements for data centres. Geonoise works independently of IAC and does not recommend suppliers.

Request a project quotation

Everything in this family is made to a project specification. Send the details and we will assess it. Goods are supplied to the project for your contractor to fit.

Contact us