Silencers for HVAC systems, industrial plant and pressure venting, selected on attenuation together with pressure drop and self-generated noise — not on length alone.

  • The selection figure is Dynamic Insertion Loss, measured with air actually flowing, paired with Self-Noise, the sound the silencer itself generates. Selecting on a no-flow attenuation figure gives an answer that does not match the site.
  • Attenuation in the first five octave bands is generally higher in reverse flow than in forward flow, so return-air systems can often take a shorter and cheaper selection.
  • Low-frequency ranges are engineered specifically for the 63 Hz, 125 Hz and 250 Hz octave bands, which are usually the bands that set the length of the unit in practice.
  • Pack-less silencers are reactive units with no infill or lining at all, for systems where fibre migration cannot be tolerated or where the airstream would attack a conventional lining.
  • Clean-Flow units encapsulate the fill completely and add a honeycomb standoff, so exposed surfaces can be cleaned. That is the range for operating theatres, recovery rooms and clean rooms.
  • Acoustic louvres exist for openings where airflow has to be preserved, not where maximum attenuation is wanted. Those two things trade against each other every time.
  • This is project work. For small quantities there is usually a better-value route than us, and we will say so.

Where this is specified

  • Air conditioning to high-rise buildings, hospitals and schools
  • Clean rooms, operating suites and laboratories
  • Food, electronics and semiconductor manufacturing
  • Chemical plants, refineries and areas handling flammable vapour
  • Tunnel ventilation and large axial fan systems
  • Engine test cells and outdoor plant compounds
  • Steam and pressurised gas discharge to atmosphere

Standards that define the requirement

  • ASTM E477, ISO 7235 and BS 4718 are the test methods that produce Dynamic Insertion Loss and Self-Noise ratings for duct silencers. The manufacturer states that catalogued ratings are determined under the applicable sections of these standards.
  • ASTM E84, NFPA 255 and UL 723 are surface burning characteristic tests, applied to the acoustic fill inside a silencer.
  • HVAC DW 144 and the ASHRAE guidance cover construction of medium pressure rectangular ductwork, which is what the outer casing of a rectangular silencer is built to.

These are the documents that set the requirement. Naming one is not a claim that a particular supplied item is certified to it; test evidence is issued per project.

Product lines in this family

  • Rectangular attenuators, in standard, low pressure drop and low frequency ranges
  • Circular attenuators
  • Clean-Flow rectangular attenuators for clean and hygienic systems
  • Conic-Flow circular attenuators
  • Pack-less attenuators, rectangular and circular
  • D-Duct diffuser attenuators for axial fan discharges
  • Acoustic louvres, curved and linear blade
  • Acoustic louvre doors for plant room walls
  • Pipe insulation and pipework vibration damping pads
  • Steam vent and pressure relief silencers
  • Engine and gas turbine exhaust silencers
  • Intake and discharge silencers for large industrial fans